E4810

 

Durathon Battery E4810E4810

Download

General Data

Nominal Energy

11.8

kWh

Nominal Capacity

230

Ah

Ambient Conditions

-40 to 65

℃

Humidity

<95%(no condensation)

RH

Altitude

<3,000

m

Warm-up Time

<16

hours

Max Internal Heater Power

450

W

Avg Heater Power Consumption,CDC

<10

W

Heater Power Consumption,Float

<140

W

Internal Low Voltage Disconnect

-40 to-45.6

VDC

Dimensions(H×D×W)

376×653×526

mm

Weight

122±2

kg

Battery Certifications

UL1973 Pending,CE,UL9540A

 

 

Technical Data

Power Availability/Backup

Usable Energy

10

kWh

Usable Capacity

200

Ah

Operating Voltages:

Equalizing charge

-53.1

VDC

Floating charge

-52.9

VDC

Open Circuit

-51.6

VDC

Discharge Load Range

0.6to 4.1

kW

Max Recharge Current

80

A

Projected Float Life

15

Yr

Charge Discharge Cycling

CDC Operating Voltages:

Recharge

-53.1

VDC

Charge Start

-41.2 to -45.3

VDC

Cycling Load Range

0.6to 3.1

kW

Max Recharge Current

80

A

Cycles Between Return to Top of Charge (TOC)

40

Cycles

Interconnects

Battery Terminals

Two pole,M6 Ring Terminal

Ground Connection

Standard:Single M6

Communication

RS485,CAN,DI/DO

Communication Protocol

MODBUS

Ingress Protection(IP

IP 20

Status Lights

2 LEDs